aboutsummaryrefslogtreecommitdiff
path: root/net/apcupsd
diff options
context:
space:
mode:
authorStefan Weil <sw@weilnetz.de>2016-03-26 11:53:07 +0100
committerStefan Weil <sw@weilnetz.de>2016-04-10 12:51:10 +0200
commit6d2c0fd06ffa2d12ab1a1bf156784e6949a903a1 (patch)
tree5a86c41f2f8ebec1d85f97aaead41123a28954ae /net/apcupsd
parentc48f8a318a064fbd557b9e30b2fd5b1ed6588945 (diff)
net: Fix typos (found by codespell)
Signed-off-by: Stefan Weil <sw@weilnetz.de>
Diffstat (limited to 'net/apcupsd')
-rw-r--r--net/apcupsd/files/apcupsd.conf6
1 files changed, 3 insertions, 3 deletions
diff --git a/net/apcupsd/files/apcupsd.conf b/net/apcupsd/files/apcupsd.conf
index b9acd61d6..5f478b937 100644
--- a/net/apcupsd/files/apcupsd.conf
+++ b/net/apcupsd/files/apcupsd.conf
@@ -10,7 +10,7 @@
# UPSNAME xxx
# Use this to give your UPS a name in log files and such. This
-# is particulary useful if you have multiple UPSes. This does not
+# is particularly useful if you have multiple UPSes. This does not
# set the EEPROM. It should be 8 characters or less.
UPSNAME ups1
@@ -114,7 +114,7 @@ NOLOGINDIR /etc
#
# Note: BATTERYLEVEL, MINUTES, and TIMEOUT work in conjunction, so
-# the first that occurs will cause the initation of a shutdown.
+# the first that occurs will cause the initiation of a shutdown.
#
# If during a power failure, the remaining battery percentage
@@ -133,7 +133,7 @@ MINUTES 3
#
# Note, if you have a Smart UPS, you will most likely want to disable
# this timer by setting it to zero. That way, you UPS will continue
-# on batteries until either the % charge remaing drops to or below BATTERYLEVEL,
+# on batteries until either the % charge remaining drops to or below BATTERYLEVEL,
# or the remaining battery runtime drops to or below MINUTES. Of course,
# if you are testing, setting this to 60 causes a quick system shutdown
# if you pull the power plug.